Operating InstructionsVEGAMIP R62Receiving unit- RelayDocument ID:41912Radar
Up to the time of installation, the packages must be left closed andstored according to the orientation and storage markings on theoutside.Unless othe
With high process temperatures exceeding 80 °C, you have to use amounting adapter for the emitting and the receiving unit. The mountingadapter can onl
4 Mounting4.1 General instructionsWith instruments with threaded process fitting, suitable tools must beapplied for tightening the hexagon.Warning:The
The VEGAMIP 62 requires a minimum product strength to detectdifferent products.Dependent on the medium there will be a respective productthickness.The
Fig. 5: Bulk solids vessel of plasticIn metal vessels, you have to mount VEGAMIP 62 on flanges orthreaded sockets. It is also possible to measure throu
ACBFig. 6: Installation in front of a vessel windowA Window of non-conductive material, for example, glass, plastic, etc.B Mounting with condensation
1 234Fig. 8: VEGAMIP 62 - threaded version G1½ A1 Polarisation marking2 Instrument hexagon3 Locknut4 Process seal1 Insert the supplied process seal (1
21Fig. 9: Front flush installation1 Unfavourable installation - bulk solid can settle in front of the sensor2 Correct front flush installationIf a front
212211Fig. 10: Front flush installation1 Plastic or ceramic material2 Fixing screw (if technically possible)In very abrasive products, VEGAMIP 62 shoul
12Fig. 11: Installation with vessel vibrations1 Anti vibration blocks or rubber buffers2 Window of non-conductive material, for example, glass, plastic
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
Polarisation directionThe emitting unit emits electromagnetic waves. The polarisation planeis the direction of the electrical wave component. Its posi
45°1 2Fig. 14: Possibilities for signal deflection1 Metal plate for signal deflection of the microwave signal2 Bent antenna extension1 Mark the holes ac
Tip:Mount the wall mounting plate so that the cable entry of the sockethousing points downward. Rain and condensation water can thus drainoff. The sock
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
4 Insert the cable into the sensor through the cable entryFig. 16: Connection steps 4 and 55 Insert the wire ends into the terminals according to the
2 Remove the housing socket from the mounting plate321Fig. 17: Remove the mounting plate from the housing socket1 Screws2 Wall mounting plate3 Cable g
5.3 Wiring plan receiving unit1 2 3 42314Fig. 18: Connection of the sensor in the housing base (external housing)1 White (terminal 2)2 Brown (terminal
Fig. 20: The electronics is located in the housing of the processing unitWe recommend connecting VEGAMIP 62 in such a way that theswitching circuit is
If ncecssary, a correspondingly dimensioned resistor must beconnected in parallel to the PLC input. With a voltage UBvon 24 V anda PLC inner resistanc
6 Setup6.1 Adjustment elementsThe figures in brackets refer to the following illustration.6798451231L N3(-)( )4 5 6 7 82+34 5 6 7 8Fig. 23: Electronic
Safety instructions for Ex areasPlease note the Ex-specific safety information for installation andoperation in Ex areas. These safety instructions are
With the mode switch (max./min.) you can change the switching statusof the relay. You can set the required mode according to the "Functionchart&q
Level Switching status Signal lamp - Re-lay (yellow)Mode min.Dry run protection53 4(8)(6) (7)Relay deenergizedFailure of the supplyvoltage(max./min. m
Press the respective key until the indication is within the LED indicationstrip. This means one or two LEDs on the LED indication strip will lightup.C
Fig. 38: LED indication strip - Setting for products with good signal dampingIf there is strong buildup during operation, adjustment with buildup isre
By means of the LED indicating board, you can adjust the switchingdelay.Push the two keys (7) and (8) simultaneously for approximately 2 suntil the LE
7 Maintenance and fault rectification7.1 MaintenanceIf the device is used correctly, no maintenance is required in normaloperation.7.2 Remove interfere
Error Cause RectificationInstrument switches fre-quently with certain levelsWave movements in thevesselAdjust or increase switching delayEffects through
8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process
- Seal between housing and housingcoverNBR (stainless steel housing), silicone (Alu/plastichousing)- Ground terminal 316LSensor length See chapter &qu
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
Contact material (relay contacts) AgNi (Au plated) or AgSnO (Au plated)Modes (switchable)- max. Max. detection or overflow/overfill protection- min. Min
Electromechanical dataCable entry/plug3)- instrument housing- Single chamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopper
- External housing IP 65- Housing base - external housing IP 68 (1 bar)Overvoltage category IIIProtection class IApprovalsInstruments with approvals c
9.2 DimensionsVEGAMIP 62, housing versions~ 69 mm(2 23/32")ø 77 mm(3 1/32")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2 23/32")ø 77 mm(
External housing90 mm (3.54")110 mm (4.33")~ 66 mm (2.6")59 mm (2.32")12Fig. 42: External housing - receiving unit1 Instrument hou
VEGAMIP 6222mm(0.87")83mm (3.27") SW 46 mm(1.42") SW 46 mm(1.42") SW 60 mm(1.42") G1½ A1½ NPT83mm (
VEGAMIP 62214315 mm(0.59")98 mm(3.86")170 mm / 300 mm(6.69") / (11.81") 19 mm(0.75")ø 75 mm(2.95")ø 115 mm(4.53")9
VEGAMIP 62mminch38 mm (1.50")22 mm (0.87")SW 46 mm(1.81")8.50"16.93"3.94" ø1.58"ø1.89"ø2.95"ø3.74"4.
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
INDEXAAbrasion 18Accessory- Flanges 10- Protective cap 10Adjustment 30Application area 7BBending 20Buildup 16CCable 23Cable screening 23EElectronics m
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
50 VEGAMIP R62 • - RelayIndex41912-EN-120228
VEGAMIP R62 • - Relay 51Index41912-EN-120228
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
The emitting frequencies of the sensors depend on the model, but areall in the K band range. The low transmitting power lies far below theinternationa
3 Product description3.1 StructureThe type label contains the most important data for identification anduse of the instrument:l Article numberl Serial
Typical applications are overfill and dry run protection. With anoperating distance of 100 m, VEGAMIP 62 can be used, for example,in bulk solids silos
Several antenna versions are available for different applications.1 23 54Fig. 2: Antenna versions1 Threaded version - internal horn antenna with PTFE c