Operating Instruction
s
VEGABAR 14
Document ID:
22441
Process pressur
e
Przeglądanie stron 0
1 2 3 4 5 6 ... 24 25

Podsumowanie treści

Strona 1

Operating InstructionsVEGABAR 14Document ID:22441Process pressure

Strona 2

Fig. 2: Installation of VEGABAR 1410 VEGABAR 144 Mounting22441-EN-111006

Strona 3

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Strona 4

Warning:Within galvanic plants as well as vessels with cathodic corrosionprotection there are considerable potential differences. Considerablyequalisat

Strona 5

2314Fig. 4: Connection to thescrew terminals1 Cable gland2 Plug housing3 Plug insert4 Plug seal7 Snap the plug insert into the plug housing and insert

Strona 6

4321321Fig. 5: Loosen the pluginsert1 Plug insert2 Strain relief3 Cable gland4 Plug housing5 Remove approx. 5 cm of the cable mantle, strip approx. 1

Strona 7

Information:Note thecorrect arrangement, see illustration9 Tighten the screws on the strain relief and cable entry10 Hook in the cover and push onto t

Strona 8

Wire colour ConnectorBrown 1White 2Blue 3Black 441223Fig. 9: Wiring plan cableoutlet1)1 brown (+) power supply and signal output2 blue (-) power suppl

Strona 9

6 Set up6.1 Setup stepsAfter mounting and electrical connection, VEGABAR 14 is ready foroperation.VEGABAR 14 delivers a current of 4 … 20 mA correspon

Strona 10

7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov

Strona 11

? Current signal 22 mAl electronicsmodule or measuring cell defectiveà Exchange the instrument or send it in for repairIn Ex applications, the regulat

Strona 12

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Strona 13

8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Strona 14

9 Supplement9.1 TechnicaldataGeneral dataParameter, pressure Gauge pressure, absolute pressure, vacuumMeasuring principle Ceramic-capacitive, dry meas

Strona 15

Range 3.8 … 20.5 mAFault signal 22 mASignalresolution 5 µAMax. output current 22 mARun-up time approx. 2 sDead time ≤ 10 msStep response time ≤ 20 ms

Strona 16

Nominal range Overload capacity, max.pressureOverloadcapacity, min.pressure-1 … 25 bar/-1 … 2.5 MPa 130 bar/13 MPa -1 bar/-100 kPa-1 … 40 bar/-1 … 4 M

Strona 17

Ambient conditionsAmbient temperature- Version with plug connector -20 … +85 °C (-4 … +185 °F)- Version with cable outlet -20 … +60 °C (-4 … +140 °F)S

Strona 18

10005007502508 141210 16 18 20 22 24 26 28 30ΩV213Fig. 10: Voltage diagram1 Voltage limit2 Operatingvoltage3 Max. loadElectrical protective measuresPr

Strona 20

9.2 Dimensions .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Supplementary documentationInformation:Supplementary documents appropriat

Strona 21

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Strona 22

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Strona 23

2.5 Safety labelon the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l

Strona 24

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGABAR 14 process pressure transmitterl depending on the version, with plug con

Strona 25

The sensor element is the CERTEC®measuring cell with ruggedceramic diaphragm. The process pressure causes a capacitancechange in the measuring cell vi

Strona 26

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and