Strona 1 - Operating Instruction

Operating InstructionsVEGABAR 61Foundation FieldbusDocument ID:28258Processpressure/Hydrostaticp

Strona 2 - Contents

l via a Linking devicewith HSE (High speedEthernet) and addition-al power supply ac-cording to IEC 61158-2The DD (Device Descriptions) and CFF (capabi

Strona 3

The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foilis also used. Di

Strona 4 - 1 About this document

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Strona 5 - 2 For your safety

Ventilation for the measuring cell is realised by means of a filterelementin the socket of the electronics housing. Ventilation for theelectronics hous

Strona 6

12Fig. 4: Temperature ranges1 Process temperature2 AmbienttemperatureDanger:Instrumentsin the version "Oil and grease free for oxygen" shoul

Strona 7

For mounting, proceedas follows:1 Position VEGABAR 61 with tube isolating diaphragm2 Tighten the threaded fittings step-by-step once on the right and o

Strona 8 - 3 Product description

90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template

Strona 9 - 3.2 Principle of operation

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Strona 10 - Ethernet) and addition

In systems without potential equalisation, connectthe cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne

Strona 11 - 28258-EN-081209

The electrical connection is finished.Fig. 6: Connection steps 6 and 7Proceedas follows:1 Loosen the four screws on the housing socket with an Allen ke

Strona 12 - 4 Mounting

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Strona 13

2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Strona 14 - 4.2 Mounting steps

5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s

Strona 15

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inter

Strona 16

123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Strona 17 - 5 Connecting to power supply

312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Strona 18 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1

Strona 19

121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Strona 20

+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal

Strona 21 - 5.3 Wiring plan, single

I²CDisplayTyp :1 2 5 6 7 8BusSim.456123Fig. 21: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C int

Strona 22

1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Strona 23

7 Setup with PACTwareand other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . . . . . .467.2 Parameter adjustment

Strona 24

5.8 Switch on phaseAfter VEGABAR 61 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30s

Strona 25

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Strona 26

Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo

Strona 27

6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Strona 28

6.4 Setup procedureVEGABAR 61 can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bec

Strona 29

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Strona 30 - 5.8 Switch on pha

The adjustment unit is hence switched over from bar to m.Proceedas follows to select the temperature unit:5)à Activate the selection with [OK] and sel

Strona 31 - 6.1 Short description

aborted with [ESC] or the displayed limit value can be accepted with[OK].Proceed as follows:1 Edit the % value in the menu item "Max. adjustment&

Strona 32

Information:Thesteps 1, 3 and 4 are not necessary for instruments which arealready preset according to customer specifications!You can find the data on

Strona 33 - - Select editing position

2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displayed.UnitUnit of measurementbar▼Temperature unit°

Strona 34 - 6.4 Setup procedur

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Strona 35

Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar value with [+] and [->].3 Confirm with [+] and move to span adjustment with

Strona 36

This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme

Strona 37 - 0000.0 mbar

Menu section Function Reset valueApplication no resetFactory settingLike basic adjustment, furthermore special parameters are reset todefault values.9

Strona 38

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a

Strona 39

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen

Strona 40

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Strona 41 - Copy sensor data?

7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl

Strona 42

Necessary components:l VEGABAR 61l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment

Strona 43 - 6.5 Menu schem

8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application

Strona 44

? Measured value on the indicating and adjustment module does notcorrespondto the value in the PLCl The menu item "Display - Display value"

Strona 45 - 6.6 Saving the pa

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Strona 46 - 7.1 Connecting the PC

Ordering and exchange are possible with or without sensor serialnumber. The electronics module with serial number includes order-specific data such as

Strona 47

l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "

Strona 48 - 8.2 Remove interferences

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Strona 49

10 Supplement10.1 TechnicaldataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range ceramic-

Strona 50 - 8.5 Instrument repair

Channel Numbers- Channel 1 Primary Value- Channel 2 Secondary Value 1- Channel 3 Secondary Value 2- Channel 4 Temperature ValueTransmission rate 31.25

Strona 51

Input variableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal measuring range:- percentage value -10 … 110 %- pressure

Strona 52 - 9 Dismounting

Nominal range Overload, max. pressure Overload, min. pressure0 … 2.5 bar/0 … 250 k Pa 50 bar/5000 kPa0 bar abs.0 … 5 bar/0 … 500 kPa 65 bar/6500 kPa0

Strona 53 - 10 Supplement

Thermal change zero zignal, referencetemperature 20 °C (68 °F):- In the compensated temperature range0 … +100 °C (+32 … +212 °F)< 0.05 %/10 K x TD-

Strona 54

- Flange 1" 150 lbs RFANSI B16.5; withextension 2", 3"1.8- Flange 2" 150 lbs RF ANSI B16.5; withextension 2"2Temperature coeffi

Strona 55

Electromechanical data - version IP 66/IP 67Cableentry/plug17)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopp

Strona 56

2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu

Strona 57

Connection cable- Configuration fourwires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm²

Strona 58

Adjustment elements 4 keysProtectionclass- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Pol

Strona 59

For these instruments, the corresponding approval documents have to be taken into account.These are part of the delivery or can be downloaded underwww

Strona 60

10.2 Information on Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function bloc

Strona 61

Secondary_value_2scale_in_0 scale_in_100 Sensor_value0 %100 %bar0,500-0,5000%100%scale_in_100scale_in_0Fig. 30: Adjustment VEGABAR 61Parameter listThe

Strona 62

l sensor_range- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'-

Strona 63 - 10.2 Information on Found

- Highest calibrated value. For calibrationof the high limit point you give the high measurementvalue (pressure) to the sensor and transfer this point

Strona 64

10.3 DimensionsHousingin protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77

Strona 65

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5

Strona 66

IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Strona 67 - 10.3 Dimensions

2.10 Environmental instructionsProtectionof the environment is one of our most important duties. Thatis why we have introduced an environment manageme

Strona 68

VEGABAR 61 - flangeversion122mm (4 51/64") 122mm (4 51/64") 51mm (2 1/64") 3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/

Strona 69

VEGABAR 61 - flangeversion3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/8"4 3/4"6 63/4"3 7/8"2 9/32" 2 43/64&qu

Strona 70

VEGABAR 61 - tube isolating diaphragm 14 31/64" 1 13/16" 1 1/32"5 33/64" 2 3/64" 1 17/64"6 9/64" 2 3/4" 1 31/3

Strona 71

VEGABAR 61 - tube isolating diaphragm 24 31/64" 5 3/64" 1 1/32"6 9/64" 6 11/16" 1 31/32"6 17/32" 7 11/64" 3 3/

Strona 72

VEGABAR 61 - tube isolating diaphragm 3128 mm (5 3/64")M55x2ø 56mm (2 13/64")ø 44,5mm (3 3/4")~ 132 mm (5 13/64")ø 38,5 mm (1 33/6

Strona 73

VEGABAR 61 - hygienic fittingRV115 mm (4 17/32")ø 78 mm (3 5/64")Fig. 39: VEGABAR 61 - RV = bolting according to DIN 11851VEGABAR 61 • Founda

Strona 74

VEGABAR 61 - cell isolating diaphragm135 mm (5 5/16")100 mm (3 15/16")b4 17/32"45/64" 2 43/64"5 29/32"45/64" 3 15/3

Strona 75

VEGABAR 61 - threaded versionSW32SW41SW55SW55G¾BG1B1½”NPTG1½B ø 22 mm (0.87") ø 32 mm (1.26")20 mm(0.79")~105 mm(4.13")~105 mm(4.7

Strona 76

VEGABAR 61 - Threaded versionwith temperature adapterSW27G1Aø 26 mm (1 1/32")LFig. 42: VEGABAR 61 - threaded version withtemperature adapter. The

Strona 77 - GD/GF GN

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Strona 78

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 61 pressure transmitterl Documentation- this operating instructions m

Strona 79 - 10.5 Trademark

80 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209

Strona 80

VEGABAR 61 • Foundation Fieldbus 8110 Supplement28258-EN-081209

Strona 81

82 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209

Strona 82

VEGABAR 61 • Foundation Fieldbus 8310 Supplement28258-EN-081209

Strona 83

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Strona 84 - ISO 9001

l Article number instrumentl Technical data: Measuring range, process pressure, processtemperature, signal output, voltage supply, protection, protect