Operating InstructionsRadiation-based sensor for continuous level and interface measurementSOLITRAC 314 … 20 mA/HART - four-wireWith SIL qualicationD
103 Product descriptionSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119• Relative humidity 20 … 85 %3.5 Accessories and replacement partsThe d
113 Product descriptionSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119responsibleauthority(inGermany,forexample,ocesforenviron-mental
124 MountingSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311194 Mounting4.1 General instructionsThe source container is part of the measuring sy
134 MountingSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311194.2 Mounting instructionsNote:Along with the planning, our specialists will analys
144 MountingSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119To measure the level in very high vessels, multiple instruments can be cascaded.Cas
154 MountingSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119On vessels with temperature insulation, the sensor and the source container should
165 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311195 Connecting to power supply5.1 Preparing the connectionAlways
175 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119If potential equalisation currents are expected, the connection o
185 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311191Fig. 6: Connection steps 4 and 51 Locking of the terminal block
195 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Information:The terminal blocks are pluggable and can be detached
2ContentsSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Contents1 About this document1.1 Function ...
205 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Instruments with intrinsically safe current outputYoucannddet
215 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311195.3 Connection - Level detectionNon-Ex instruments and instrumen
225 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311191124/L/NPE562211122122 1920 18 17 14 1316 15 1221443Fig. 13: Elec
235 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119The instrument acts as Master and all other instruments operate a
245 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119112456 910112211122122 1920 18 17 14 1316 15 12112456 91011221112
255 Connecting to power supplySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Information:For example, a radial connection would be also possib
266 Functional safety (SIL)SOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311196 Functional safety (SIL)6.1 ObjectiveIn case of dangerous outages,
276 Functional safety (SIL)SOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119• 4 … 20 mA current output6.4 Safety concept of the parameterizatio
286 Functional safety (SIL)SOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119All parameters changed by the operator are marked automatically so t
297 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311197 Set up with the display and adjustment modu
3ContentsSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311199.2 Status messages ...
307 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311197.2 Adjustment system12Fig. 17: Display and a
317 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Information:Inthisoperatinginstructionsman
327 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Otherwise the instrument remains in the releas
337 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Through this selection, the sensitivity of the
347 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Enter in the menu window "Max. process va
357 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Select "Linearization - New"toente
367 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Because you have already set the background ra
377 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119If you know the level at a certain height, you
387 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119You can choose "no" reference value.
397 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Inasecondstep,allmodiedsafety-relevant
41 About this documentSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311191 About this document1.1 FunctionThis operating instructions manual prov
407 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119points (Delta I). The value is an indication f
417 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Additional adjustmentsIn this menu item, the P
427 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Menu Menu item Default valueSetup Measurement
437 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119With this function• Load parameter adjustment
447 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119adjustment module. To do this you need PACTwar
457 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Setup: Settings, e.g. for measurement loop nam
467 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119When the output is active, the instrument has
477 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Additional adjustmentsWhen a reset is carried
487 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Menu Menu item Default valueSetup Measurement
497 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Information:Inthisoperatinginstructionsman
52 For your safetySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311192 For your safety2.1 Authorised personnelAll operations described in this o
507 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Otherwise the instrument remains in the releas
517 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Through this selection, the sensitivity of the
527 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119the adjustment of the sensor with full status
537 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Thechangebetweenthetwostatusesissucien
547 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119You can enter the adjustment point (ct/s) manu
557 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Dry run protection = the relay will deenergise
567 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119DisplayWith this parameter you can change the
577 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Pulse rate of the sensorCurrent outputSwitchin
587 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Basic settings: Resetting of the parameter adj
597 Set up with the display and adjustment moduleSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119If the measured value is outputted via the 4 …
62 For your safetySOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Only with class A instruments:The device is a class A instrument designed for
608 Setup with PACTwareSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311198 Setup with PACTware8.1 Connect the PC213Fig. 18: Connection of the P
618 Setup with PACTwareSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119• SOLITRAC 31• PCwithPACTwareandsuitableVEGADTM• VEGACONNECT4• HA
628 Setup with PACTwareSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Fig. 20: Example of a DTM viewAll device DTMs are available as a free-of
639 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311199 Diagnostics and service9.1 MaintenanceIf the device is used corre
649 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Maintenance:Duetoexternalinuences,theinstrumentfunctionisl
659 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119CodeText mes-sageCause RecticationF036Faulty pro-gram memory – Erro
669 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119CodeText mes-sageCause RecticationF120Filter time error – Faulty or
679 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119CodeText mes-sageCause RecticationS017Accuracy outside the specica
689 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Error Cause Rectication4 … 20 mA signal missingElectrical connec-ti
699 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Sinceweoerthisserviceworldwide,thesupportisprovidedinEng
73 Product descriptionSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-1311193 Product description3.1 CongurationThenameplatecontainsthemostim
709 Diagnostics and serviceSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119• Printandlloutoneformperinstrument• Clean the instrument an
7110 DismountingSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-13111910 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of da
7211 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-13111911 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.443
7311 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-13111912LFig. 22: Data of the input variable1 Min. level (red marking line)2 Max. le
7411 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Output variable - Level measurementOutput signals 4 … 20 mA/HART - active; 4 … 2
7511 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119 Ʋ Max. 3 A AC, 1 A DCBreaking capacity Ʋ Min. 50 mW Ʋ Max. 750VAAC,40WDCIf
7611 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Process temperature (measured on the detector tube)-40 … +60 °C (-40 … +140 °F)W
7711 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Voltage supplyOperating voltage 20…72VDCor20…253VAC,50/60HzInterpola
7811 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Aluminium and stainless steel housing242,5 mm (9.55")54,5 mm(2.15")9 m
7911 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119SOLITRAC 3122 mm(0.87")36 mm(1.42")ø 76,2 mm(3")L242,5 mm (9.55&q
83 Product descriptionSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119• Modicationstatuselectronicsfrom-07Theinstrumentisavailableind
8011 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119SOLITRAC 31 - Mounting example220 mm(8.66")70 mm(2.76")101,6 mm(4.00&q
8111 SupplementSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-13111911.3 Industrial property rightsVEGA product lines are global protected by indus
82INDEXSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119INDEXAAccessories – External indicating unit 10Adjustment 33 – System 30Adjustment da
83INDEXSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Summation Slave 43TTime 41, 57Type plate 7UUnit 51Units 33VVoltagesupply16, 77WW
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany43387-EN-131119All statements concerning scope of delivery, application, practi
93 Product descriptionSOLITRAC 31 • 4 … 20 mA/HART - four-wire43387-EN-131119Due to the physical properties of the radioactive radiation, the pulse ra