7 Setting up sensor and Modbus interface with PACTware
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
The connection of the PC to the RS 485 cable is carried out via a
standard interface adapter RS 485/USB.
Scope of the parameter adjustment:
Sensor electronics
Modbus electronics
Information:
For the parameter adjustment it is absolutely necessary to separate
the connection to the RTU.
RS485
USB
1
2
3
4
5
Fig. 21: Connection of the PC via the interface adapter to the RS 485 cable
1 Interface adapter RS 485/USB
2 USB cable to the PC
3 RS 485 cable
4 Sensor
5 Voltage supply
7.2 Parameter adjustment with PACTware
For parameter adjustment of the sensor via a Windows PC, the con-
guration software PACTware and a suitable instrument driver (DTM)
according to FDT standard are required. The up-to-date PACTware
version as well as all available DTMs are compiled in a DTM Collec-
tion. The DTMs can also be integrated into other frame applications
according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older rmware versions. You can download
the latest instrument software from our homepage. A description of
the update procedure is also available in the Internet.
Further setup steps are described in the operating instructions manu-
al "DTM Collection/PACTware" attached to each DTM Collection and
which can also be downloaded from the Internet. Detailed descrip-
tions are available in the online help of PACTware and the DTMs.
To the RS 485 cable
Prerequisites